Use this link to cite:
http://hdl.handle.net/2183/334 Boundary element formulation for the analysis of transferred
potentials in electrical installations
Loading...
Identifiers
Publication date
Advisors
Other responsabilities
Journal Title
Bibliographic citation
Advances in engineering software, vol. 35, n. 10-11 (Oct.-Nov. 2004), p. 601-667
Type of academic work
Academic degree
Abstract
[Abstract] In this work we present a BEM numerical formulation for the analysis of a common problem in electrical engineering practice, that is, the existence of transferred earth potentials in a grounding installation [IEEE Guide for safety in AC substation grounding (2000)]. The transfer of potentials between the grounding area to outside points by buried conductors, such as communication or signal circuits, neutral wires, pipes, rails, or metallic fences, may produce serious safety problems [Comput Methods Appl Mech Eng, 174 (1999) p. 73]. Thus, in this paper we summarize the BE numerical approach and we present a new technique for the transferred potential analysis. Finally, we show some examples by using the geometry of real grounding systems.