Use this link to cite:

http://hdl.handle.net/2183/334

Boundary element formulation for the analysis of transferred potentials in electrical installations

Loading...
Thumbnail Image

Identifiers

Publication date

Advisors

Other responsabilities

Journal Title

Bibliographic citation

Advances in engineering software, vol. 35, n. 10-11 (Oct.-Nov. 2004), p. 601-667

Type of academic work

Academic degree

Abstract

[Abstract] In this work we present a BEM numerical formulation for the analysis of a common problem in electrical engineering practice, that is, the existence of transferred earth potentials in a grounding installation [IEEE Guide for safety in AC substation grounding (2000)]. The transfer of potentials between the grounding area to outside points by buried conductors, such as communication or signal circuits, neutral wires, pipes, rails, or metallic fences, may produce serious safety problems [Comput Methods Appl Mech Eng, 174 (1999) p. 73]. Thus, in this paper we summarize the BE numerical approach and we present a new technique for the transferred potential analysis. Finally, we show some examples by using the geometry of real grounding systems.

Description

Rights